Electric motor with P2>=5,5 kW with star-delta startingIn Y starting only, in D operation onlyLock the switch in position ON to prevent unintended switch OFF (lock is not in scope of delivery)
* 24VDC (+30/-20%)** NO/NC are intended to control position of actuator`s service switch (ON - OFF)Warning: the control voltage 24VDC to open or close hatch cover should apply max. 6 minutes.This is to ensure by control system (use actuator`s internal floating limit switches as indication of cover position to cut off the control voltage). More see instructions (current, intermittence).The connection cable to service switch calculate with max. 1V voltage drop at max. load!Operating mode for peak load at 25°C ambient: S2 1 minOperating mode for continuous load at 40°C ambient: S3 5% (example: open in 30s, then wait 9min 30s)Max. current of actuator(s) at SL 1000 (rated MRH load):MRH 400-630: 4AMRH 710-800: 6AMRH 1000: 8AMRH 1120-1250: 2x8A=16A
*** drawn position - closed hatch1-2 opened, 2-3 closed in closed hatch position1-2 closed, 2-3 opened in opened hatch position1-2 closed, 2-3 closed in any intermediary position of the hatch cover1-2, 4-5 opened, 2-3, 5-6 closed in closed hatch position (MRH 1120-1250 only)1-2, 4-5 closed, 2-3, 5-6 opened in opened hatch position (MRH 1120-1250 only)1-2, 4-5 closed, 2-3, 5-6 closed in any intermediary position of the hatch cover (MRH 1120-1250 only)Potentialfree NC contacts, load capacity 24VDC/1AFunctions of the actuator`s service switch:Position 0: stop (NO - opened contact, NC - closed contact) - SAFETY POSITIONPosition 1: open hatch cover (NO - closed contact, NC - opened contact) - WARNING!Position 2: close hatch cover (NO - opened contact, NC - closed contact) - DANGER!